SAMPLE REPORT. Generated by ATLAS-OT v1.1.3 on October 29, 2026, from the product’s built-in example data (a synthetic facility, “Example Houston One”). No real facility was assessed. The format, grading, fix list and evidence structure are the real deliverable. ATLAS-OT’s live InternetDB mode was verified against the real API the same day. Back to bangre-nooma.com

ATLAS-OT Exposure Report

Operator: Example Operator LLC
Facility: Example Houston One, Spring, Texas
Generated: 2026-10-29T22:25:45.005Z
Authorization: Example Authorizer, Director of Facilities - ref AUTH-EXAMPLE-001, 2026-10-28 to 2027-12-31
Scope: 203.0.113.0/24 - domains: colo.example-operator.com

Note: this scope includes private, lab or documentation ranges. This is a lab / test report, not a production assessment.

Executive summary

5 exposed OT / building system(s): 3 critical, 2 high, 0 medium, 0 low.

Sources checked: examples/shodan.example.json (import, 8 observations).
Observations: 8 received, 8 after cross-source dedupe: 6 in scope, 1 out of scope (excluded, appendix), 1 honeypot suspects (excluded, appendix), 1 in-scope IT-only services.

Finding register

#SeverityExposureSystemProductImpactFixConfidence / basisCVEs flaggedEvidence (banner)Source
1CRITICAL BACnet/IP
203.0.113.10:47808/udp
coolingBACnet Stack 1.0 Building controller for cooling / HVAC. BACnet has no authentication in its classic form: anyone who can reach it can read points and, on many devices, write setpoints. Loss or manipulation of cooling can force thermal shutdowns within minutes at modern densities.Remove BACnet/IP from the public internet. Place it behind the BMS VPN / jump host, or migrate to BACnet/SC with certificates. Firewall UDP 47808 to named management addresses only. high
protocol confirmed by banner / product data
none flagged BACnet/IP device instance 1234, vendor ExampleControls shodan
observed 2026-10-27T12:00:00.000000
2CRITICAL Modbus TCP
203.0.113.11:502/tcp
powerModbus TCP Modbus has no authentication or encryption. In a data center it commonly fronts UPS units, PDUs, meters and generator controllers: read and write access to power equipment registers. Loss or manipulation of power distribution, UPS or generation can drop the load the facility exists to carry.Remove Modbus TCP from the public internet immediately. Put power devices on a segmented OT VLAN reachable only from the DCIM / BMS network, through a jump host. high
protocol confirmed by banner / product data
none flagged Modbus device: UPS controller unit id 1 shodan
observed 2026-10-27T12:00:00.000000
3CRITICAL Niagara Fox
203.0.113.12:1911/tcp
controlNiagara Fox 4.10 Tridium Niagara station protocol. A reachable Fox service exposes the building automation station that supervises cooling, power and alarms for the facility. This is a supervisory control system: compromise here can reach the cooling and power systems it supervises.Remove Fox from the public internet. Access Niagara stations only through the vendor VPN / secure remote access with MFA. Disable Fox where FoxS or Niagara Web is used instead. high
protocol confirmed by banner / product data
CVE-2020-0000 fox version 4.10 station ExampleStation shodan
observed 2026-10-27T12:00:00.000000
4HIGH SNMP
203.0.113.13:161/udp
monitoringAPC UPS SNMP Monitoring protocol for UPS, PDU, cooling and generator equipment. SNMP v1/v2c uses guessable community strings and leaks device model, firmware and load data useful for planning an attack. Monitoring exposure blinds operators and leaks the data an attacker needs to plan a physical attack.Block SNMP at the perimeter. Use SNMPv3 with authentication inside the management network only; change every default community string (public / private). high
protocol confirmed by banner / product data
none flagged SNMP public community, model Smart-UPS, firmware 4.1 shodan
observed 2026-10-27T12:00:00.000000
5HIGH BMS web management
203.0.113.14:443/tcp
controlAutomated Logic WebCTRL Web management for a building system (webctrl) reachable from the internet. This is a supervisory control system: compromise here can reach the cooling and power systems it supervises.Remove building-system web management from the public internet. Require VPN with MFA for vendor and operator access; keep the BMS application patched. high
building-system product "webctrl" identified in service data
none flagged WebCTRL building automation login shodan
observed 2026-10-27T12:00:00.000000

Compliance and insurance view

#1 NIST CSF 2.0: PR.IR-01, PR.AA-03, PR.AA-05, ID.RA-01 (Network protection (PR.IR), authentication and access control (PR.AA), risk assessment (ID.RA))
Insurance relevance: Building automation / HVAC controls reachable from the public internet; remote vendor access without MFA

#2 NIST CSF 2.0: PR.IR-01, PR.AA-03, PR.AA-05, ID.RA-01 (Network protection (PR.IR), authentication and access control (PR.AA), risk assessment (ID.RA))
Insurance relevance: Power infrastructure (UPS, PDU, generator) controls reachable from the public internet; network segmentation of OT

#3 NIST CSF 2.0: PR.IR-01, PR.AA-03, PR.AA-05, PR.DS-02, ID.RA-01 (Network protection (PR.IR), authentication and access control (PR.AA), data security (PR.DS), risk assessment (ID.RA))
Insurance relevance: Supervisory / building management system exposed to the internet; MFA for remote access; vendor remote-access controls

#4 NIST CSF 2.0: PR.IR-01, PR.AA-03, PR.DS-02, DE.CM-01 (Network protection (PR.IR), authentication (PR.AA), data security (PR.DS), continuous monitoring (DE.CM))
Insurance relevance: SNMP v1/v2c with default or guessable community strings (public / private) on infrastructure devices

#5 NIST CSF 2.0: PR.IR-01, PR.AA-03, PR.AA-05, PR.DS-02, ID.RA-01 (Network protection (PR.IR), authentication and access control (PR.AA), data security (PR.DS), risk assessment (ID.RA))
Insurance relevance: Supervisory / building management system exposed to the internet; MFA for remote access; vendor remote-access controls

This view maps findings to framework categories and common questionnaire topics. It is not a certification or an audit opinion.

Appendix - excluded observations

Out of scope (1): 198.51.100.9:47808/udp. These were never treated as findings about this facility.

Honeypot suspects (1): 203.0.113.99:47808/udp.